The generator lugs (H1, H2, H3) are the true phases. Each switch terminal has a disconnect blade between its line and load sides; the blades close with the Close switch button. The optional feed-through wires carry the line side of the switch on to the next substation switch. The switch terminals show what each conductor is labeled in the switch, which may not match the generator if the feeds are crossed.
Each coil point is marked 1 for the top end and 2 for the bottom. The black dot marks the polarity end, which is the top by default; advanced users can move it under Polarity ends. The badge next to a point shows the phase it actually feels. Each secondary bus is in phase with the voltage its coil sees from its 1 end to its 2 end.
Tap a switch terminal, then a coil point, to run a lead. Tap two coil points for a jumper. Tap a generator lug, then a switch terminal, to move a feed. Tap any wire to remove it.
Polarity ends (advanced)
You normally won't need to change these. The manufacturer's internal connections and terminal markings already account for polarity. It matters when you are reconnecting taps, rebuilding or rewinding a transformer, or combining two transformers whose vector group is unknown.
The polarity end of a coil is the terminal that swings positive at the same instant as the matching polarity terminal on the other winding. Each secondary bus follows its coil from the polarity end to the other end, so moving the polarity end turns that bus 180°.
It is often shown by a dot (as on this diagram), an H1 or X1 terminal marking, a ± sign, a "polarity" tag, or a painted or colored terminal. Single-phase nameplates may also say additive or subtractive polarity. These markings may not always be present, and on older or rewound units they can be missing, painted over or wrong.
When the polarity end is unknown, a DC kick test can identify it. With the transformer de-energized, isolated and locked out, isolate the coil you are testing from the other coils if possible by removing the jumpers or bus connections that tie it into the bank. Other windings still connected can carry part of the pulse and give a weak or misleading kick. Then connect an analog DC voltmeter across one winding, and briefly connect a small battery (such as 6 to 9 V) across the other winding. If the meter kicks upscale when the battery connects, the battery + lead and the meter + lead are on like-polarity terminals. Break the battery connection carefully, since the winding can kick back a high voltage when the circuit opens.
Dead short!
A vector group like Dyn1 describes the bank: D is a delta high side, y is a wye low side, n means the neutral is brought out, and the number times 30° is how far X1 lags H1.
Delta-wye banks only come in odd numbers: Dyn1, 3, 5, 7, 9 and 11. Dyn1 is the ANSI standard. A bank that reverses rotation is named for the standard scheme plus the swap that caused it, such as "Dyn1, A/B reversed."
Selecting a different arrangement from the dropdown updates the wiring scheme and the delta triangle, with straight generator feeds, but it does not change the source rotation from the generator. The A/B reversed and B/C reversed options make the swap with the Super J wires on the load side of the switch.
Swap A/B and Swap B/C also trade Super J wires on the load side of the switch: Swap A/B trades the wires on the terminals labeled H1 and H2, and Swap B/C trades H2 and H3. MV cables only move when you move them by hand, and any reversal that causes is still recognized and named.
Vector groups assume an H1 → H2 → H3 source and use your bus names. Until all three buses are named, left, middle and right are read as A, B and C.
High side delta
Each coil is drawn on the side of the triangle between the two supply lines it is connected across. The corners are the true generator phases.
A proper delta has exactly one coil on each side. If two coils share a side, or a coil has the same line on both ends, the bank will not produce balanced three-phase.
High side source (measured at the generator)
The generator supplies 13,800 V line to line.
CW means H1 peaks first, then H2, then H3. Set the generator rotation under the wiring diagram to match what is measured at the generator set.
Low side output (measured at the low side bus)
The secondary is 480Y/277 V.
The order of the peaks gives the low side rotation. On a delta-wye bank the low side is always shifted from the high side by an odd multiple of 30°.
Energize the generator to see what the secondary puts out.
Test results
A good 480Y/277 V bank reads 277 V line to neutral and 480 V line to line on every phase. Readings more than 5 V off are marked.
Two low line-to-line readings that share a bus usually mean that coil is backwards compared with the other two. A bus reading 0 V means its coil has the same line on both ends.